The Load Configuration screen

Press the Load Calculation button under the room list to open the load configurations pane on the left of the window. A project can hold several configurations, for example one per design case you want to compare, and each one is a complete set of the settings described on this page. Every configuration is a collapsible bucket with Rename, Duplicate and Delete buttons on its header. The Add button at the right end of the pane's heading adds another, and ✖ Close Calculations at the top right of the window returns to the drawing.

The Load Configuration screen

Only one configuration is open at a time. Clicking another one's title opens it, lists it last and scrolls the pane so its title is at the top; scroll up to see the others. This only changes what the pane shows: the project keeps your configurations in the order you created them.

While this screen is open, the results pane is shown under the drawing and the drawing itself is view-only, with its Edit, Redraw and Delete buttons hidden.

Each group below matches a group on the screen, in the same order. The table gives one line per field, and the Read more link opens the full explanation.

Every group starts open; click a group's title bar to fold it. Rows that do not apply are hidden rather than greyed, and a tick-box row reads a muted "off" while its box is unticked.

Config name

The name of this configuration. It is required and must be unique within the project; it appears on the bucket header and in the exported results. A name that clashes with another configuration is outlined in red with the message "Config name must be unique."

Climate & site

Climate and site

Field What it does Default Read more
Country Chooses the country whose cities are listed; blank means the building's country. The building's country Country
City Chooses the city whose weather data is used; blank means the building's city. The building's city City
Station Shows the nearest weather station and how far away it is (read-only). Pick a city to enable climate data Station
Method Which design day or days to run, and whether the worst month and hour are searched for (calculation method). Peak dry-bulb only (recommended) Method
Month The month to run at; shown for "Specific month and hour" only. May Month
Hour The hour to run at; shown for "Specific month and hour" only. 15:00 Hour
Percentile How extreme the design weather is (design percentile). 0.4% (recommended) Percentile

Summer indoor design

Summer indoor design

Field What it does Default Read more
Temperature The temperature the room is held at; sets every inside-to-outside difference. 24 °C Temperature
Humidity The humidity the room is held at; sets the moisture the fresh air must shed. 55 % Humidity

Construction

Construction

Field What it does Default Read more
Radiant time delay Whether the radiant share of each heat gain is released over the following hours. Yes Radiant time delay
Construction Light, Medium or Heavy building; picks how slowly radiant heat is released. Shown only while Radiant time delay is Yes. Medium Construction class
Partition ΔT How much cooler the space behind an internal wall is assumed to be than outdoors. 25 % Partition ΔT
Ground ΔT How much cooler the ground is assumed to be than the outdoor air. 25 % Ground ΔT

Design margins

Design margins

Field What it does Default Read more
Sensible Margin on the room's sensible (temperature) load. On, 10 % Sensible
Latent Margin on the room's latent (moisture) load. On, 5 % Latent

Coil and duct allowances

Coil and duct allowances

Field What it does Default Read more
Bypass factor Share of the air that passes the coil untreated. 0.10 Bypass factor
Min airflow What the coil does with supply air above what it needs, when a room's minimum airflow wins. Bypass the extra air around the coil Min airflow
Fixed ADP Pin the apparatus dew point instead of solving it. Off, 10 °C Fixed ADP
Supply gain Heat picked up by the supply duct, on the room sensible load. Off, 2 % Supply gain
Supply leak Air lost from the supply duct, on the room sensible and latent loads. Off, 2 % Supply leak
Fan heat Supply fan heat, on the room sensible load. Off, 5 % Fan heat
Return gain Heat picked up by the return duct, on the grand total. Off, 1 % Return gain
Return leak Air lost from the return duct, on the grand total. Off, 1 % Return leak

Winter design

Off by default: until Heating (calculate heating loads) is ticked the group shows that one line. Tick it to show the rest of the group and add a Heating Load tab to the results.

Winter design

Field What it does Default Read more
Heating Runs the winter design case alongside cooling. Off Heating
Temperature The temperature the room is held at in winter; sets every inside-to-outside difference. 21 °C Temperature
Humidity The humidity the room is held at in winter; sets how much moisture the humidifier adds. 30 % Humidity
Percentile How extreme the winter design day is. 99.6% (recommended) Percentile
Supply air The supply temperature used to check whether the cooling airflow can carry the heat. 40 °C Supply air
Margin Margin on the heat lost through the fabric and to outdoor air. On, 10 % Margin
Partition ΔT How much warmer the space behind an internal wall is assumed to be than outdoors in winter. 50 % Partition ΔT

Calculate

The Calculate button stays at the bottom of the pane, below the list, and runs the open configuration for every room in the project. It is greyed out, with the hint "Add rooms to a floor first.", until the project has at least one room. Any problems with the settings are listed in red at the end of that configuration and must be cleared before the calculation can run.

The inputs shown before a run

The question a one-floor project asks first

Before anything is calculated, a read-only window titled "Review before calculating" lists what the run is about to use: the load configuration (climate, design conditions, safety factors, coil and heating settings), each floor with its rooms, storeys, height and whether it carries a roof or a ground slab, and the window, external wall, partition wall and roof types the air-conditioned rooms use, with their U-values and other parameters, how many and how much of each. The load configuration reads as two tables side by side, tables narrow enough share a line, and each table spreads its spare width evenly over its columns, so there is less to scroll; the window takes at least 60 % of the screen's width and at most 70 % of its height, and every table shows all its rows. When some rooms are not yet marked reviewed, an amber line at the top says how many, for example "⚠ 3 rooms not reviewed"; it only informs. Nothing can be changed there: press Calculate to go ahead, or Cancel to change something first. Once the calculation starts, a spinner stays on screen until the results are in.